DATAKOM DKM-405

AED400.00

DATAKOM DKM-405 is (Original) and made in Turkey. It is a multifunctional power meter and network analyzer typically used for monitoring and controlling electrical parameters in industrial and commercial settings

Quantity

Description

DATAKOM DKM-405 is a multifunctional power meter and network analyzer typically used for monitoring and controlling electrical parameters in industrial and commercial settings.

DATAKOM DKM-405 is a precision network analyzer designed to monitor and display various AC parameters in three-phase distribution panels. It offers a comprehensive set of features suitable for both industrial and commercial applications.

Features:

  • True RMS Measurements: Ensures accurate readings for non-linear loads.
  • Total Harmonic Distortion (THD) Display: Provides harmonic analysis up to the 31st order for both voltage and current inputs.
  • Maximum Demand Display: Monitors peak demand values to assist in capacity planning.
  • Configurable Relay Output: Programmable relay functions for customized control actions.
  • Energy Pulse Output Capability: Facilitates integration with external energy management systems.
  • Optically Isolated, Configurable Digital Input: Accepts both AC and DC signals with programmable functions.
  • Active-Reactive Power Counters: Tracks energy consumption over time.
  • Hour Counter: Records total operational hours for maintenance scheduling.
  • Voltage Transformer Ratio Configuration: Allows adaptation for medium voltage applications.
  • Front Panel Programming: User-friendly interface for easy parameter configuration.
  • Reduced Panel Depth: Compact design suitable for space-constrained installations.
  • Wide Operating Temperature Range: Operates reliably in diverse environmental conditions.
  • Sealed Front Panel (IP54): Provides protection against dust and water splashes.
  • Plug-in Connection System: Simplifies installation and maintenance.

Measured Parameters:

  • Voltages:
    1. Phase-to-Phase: U12, U23, U31
    2. Phase-to-Neutral: V1, V2, V3
  • Currents:
    1. Phase Currents: I1, I2, I3
  • Power:
    1. Active Power (P): P1, P2, P3, and Total ∑P
    2. Reactive Power (Q): Q1, Q2, Q3, and Total ∑Q
    3. Apparent Power (S): S1, S2, S3, and Total ∑S
  • Power Factor:
    1. Individual Phase Power Factors: cosφ1, cosφ2, cosφ3
    2. Total Power Factor: ∑cosφ
  • Energy Counters:
    1. Active Energy (kWh): Pc1
    2. Reactive Energy (kVArh): Qc1
  • Hour Counter:
    1. Operational Hours: Hc1
  • Total Harmonic Distortion (THD):
    1. THD values for both voltage and current input parameters.

Technical Specifications:

Power Supply Input:

    1. Voltage: 170 – 275 VAC
    2. Frequency: 50 – 60 Hz nominal (±10%)

Measurement Input Range:

Voltage Inputs:

  1. 10 – 300 V AC (L-N)
  2. 20 – 520 V AC (L-L)
  3. Current Inputs: 0.2 – 5.5 A AC
  4. Frequency: 30 – 100 Hz

Accuracy:

    1. Voltage: 0.5% + 1 digit
    2. Current: 0.5% + 1 digit
    3. Frequency: 0.5% + 1 digit
    4. Power (kW, kVAr): 1.0% + 2 digits
    5. Power Factor: 2.0% + 2 digits

Measurement Range:

    1. CT Range: 5/5A to 5000/5A
    2. VT Range: 0.1/1 to 200.0/1
    3. Power Range: 0.1 kW to 6.5 MW

Power Consumption: < 4 VA

Burden:

    1. Voltage: < 0.1 VA per phase
    2. Current: < 1 VA per phase

Relay Output: 5A @ 250 VAC

Digital Input:

    1. Active Level: 5 to 30 V DC or AC
    2. Minimum Pulse Duration: 250 ms
    3. Isolation: 1000 V AC, 1 minute

Operating Temperature: -20°C to +80°C (-4°F to +176°F)

Maximum Humidity: 95% non-condensing

Degree of Protection:

    1. Front Panel: IP54
    2. Back Panel: IP30

Enclosure: Non-flammable, ROHS compliant, ABS/PC (UL94-V0)

Installation: Flush mounting with rear retaining brackets

Dimensions: 102 x 102 x 53 mm (W x H x L)

Reviews

There are no reviews yet.

Be the first to review “DATAKOM DKM-405”

Your email address will not be published. Required fields are marked *