DATAKOM DKM-405
AED400.00
DATAKOM DKM-405 is (Original) and made in Turkey. It is a multifunctional power meter and network analyzer typically used for monitoring and controlling electrical parameters in industrial and commercial settings
Description
Description
DATAKOM DKM-405 is a multifunctional power meter and network analyzer typically used for monitoring and controlling electrical parameters in industrial and commercial settings.
DATAKOM DKM-405 is a precision network analyzer designed to monitor and display various AC parameters in three-phase distribution panels. It offers a comprehensive set of features suitable for both industrial and commercial applications.
Features:
- True RMS Measurements: Ensures accurate readings for non-linear loads.
- Total Harmonic Distortion (THD) Display: Provides harmonic analysis up to the 31st order for both voltage and current inputs.
- Maximum Demand Display: Monitors peak demand values to assist in capacity planning.
- Configurable Relay Output: Programmable relay functions for customized control actions.
- Energy Pulse Output Capability: Facilitates integration with external energy management systems.
- Optically Isolated, Configurable Digital Input: Accepts both AC and DC signals with programmable functions.
- Active-Reactive Power Counters: Tracks energy consumption over time.
- Hour Counter: Records total operational hours for maintenance scheduling.
- Voltage Transformer Ratio Configuration: Allows adaptation for medium voltage applications.
- Front Panel Programming: User-friendly interface for easy parameter configuration.
- Reduced Panel Depth: Compact design suitable for space-constrained installations.
- Wide Operating Temperature Range: Operates reliably in diverse environmental conditions.
- Sealed Front Panel (IP54): Provides protection against dust and water splashes.
- Plug-in Connection System: Simplifies installation and maintenance.
Measured Parameters:
- Voltages:
- Phase-to-Phase: U12, U23, U31
- Phase-to-Neutral: V1, V2, V3
- Currents:
- Phase Currents: I1, I2, I3
- Power:
- Active Power (P): P1, P2, P3, and Total ∑P
- Reactive Power (Q): Q1, Q2, Q3, and Total ∑Q
- Apparent Power (S): S1, S2, S3, and Total ∑S
- Power Factor:
- Individual Phase Power Factors: cosφ1, cosφ2, cosφ3
- Total Power Factor: ∑cosφ
- Energy Counters:
- Active Energy (kWh): Pc1
- Reactive Energy (kVArh): Qc1
- Hour Counter:
- Operational Hours: Hc1
- Total Harmonic Distortion (THD):
- THD values for both voltage and current input parameters.
Technical Specifications:
Power Supply Input:
-
- Voltage: 170 – 275 VAC
- Frequency: 50 – 60 Hz nominal (±10%)
Measurement Input Range:
Voltage Inputs:
- 10 – 300 V AC (L-N)
- 20 – 520 V AC (L-L)
- Current Inputs: 0.2 – 5.5 A AC
- Frequency: 30 – 100 Hz
Accuracy:
-
- Voltage: 0.5% + 1 digit
- Current: 0.5% + 1 digit
- Frequency: 0.5% + 1 digit
- Power (kW, kVAr): 1.0% + 2 digits
- Power Factor: 2.0% + 2 digits
Measurement Range:
-
- CT Range: 5/5A to 5000/5A
- VT Range: 0.1/1 to 200.0/1
- Power Range: 0.1 kW to 6.5 MW
Power Consumption: < 4 VA
Burden:
-
- Voltage: < 0.1 VA per phase
- Current: < 1 VA per phase
Relay Output: 5A @ 250 VAC
Digital Input:
-
- Active Level: 5 to 30 V DC or AC
- Minimum Pulse Duration: 250 ms
- Isolation: 1000 V AC, 1 minute
Operating Temperature: -20°C to +80°C (-4°F to +176°F)
Maximum Humidity: 95% non-condensing
Degree of Protection:
-
- Front Panel: IP54
- Back Panel: IP30
Enclosure: Non-flammable, ROHS compliant, ABS/PC (UL94-V0)
Installation: Flush mounting with rear retaining brackets
Dimensions: 102 x 102 x 53 mm (W x H x L)
Reviews
There are no reviews yet.